Unistrut P2600 - Unicushion Isolation Material (25')

- Size & Finish
Availability - Specifications
- Pipe Reference
Data - Related Unistrut
Channeling - Request Quote
| Part No. |
P2600 |
25 feet per carton. Cut to length. Clamps should be oversized by 1/8" in diameter.
Unistrut® Pipe / Conduit Supports Specifications
Material:
- Unistrut pipe clamps, unless noted, are punch-press made from hot-rolled, pickled and oiled steel plates, strip or coil, and conform to ASTM specifications A1008, A575, A576, A635, or A36. The fitting steel also meets the physical requirements of ASTM A1011 SS GR 33. The pickling of the steel produces a smooth surface free from scale.
- Many items are also available in stainless steel. Consult factory for ordering information.
Application:
- Unistrut pipe clamps, pipe hangers, brackets and rollers are designed for the support of electrical and mechanical services. Supports to meet nearly every requirement can be attained using Unistrut Metal Framing components.
Design Bolt Torque:
Note: When tightening 1/4" screws used with a two piece pipe clamp, a torque of 5 foot pounds (60 inch-pounds) should be used.
Dimensions:
- Imperial dimensions are illustrated in inches. Metric dimensions are shown in parenthesis or as noted. Unless noted, all metric dimensions are in millimeters.
Design Load:
- Design load data, where shown, is based on the ultimate strength of the connection with a safety factor of 5.0, unless otherwise noted.
Electrical Metallic Tubing (EMT) - Thin Wall:
Intermediate Metallic Conduit (IMC):
Copper Tube (Type L):
Copper Tube (Type K):
Rigid Steel (Heavy Duty) Conduit:
Water Filled Pipe Support Spacing:
Conduit Support Spacing:
346-12. Supports Rigid metal conduit shall be installed as a complete system as provided in Article 344 and shall be securely fastened in place. Conduit shall be firmly fastened with 3 feet (914.4 mm) of each outlet box, junction box, cabinet, or fitting. Conduit shall be supported at least every 10 feet (3.05m).
Exception: If made up with threaded couplings, it shall be permissible to support straight runs of rigid metal conduit in accordance with Table 344.30 (B)(2), provided such supports prevent transmission of stresses to termination where conduit is deflected between supports.
Schedule 40: PVC Plastic Pipe: